There is also current isolation between the on-site bus sections to prevent multiple ground faults from leading to multiple faults. Each segment has its own fieldbus power regulator and current limit. When installing a single or redundant F8Ox module, the terminal of the on-site bus section is automatically maintained. The AnF8Op9F. Plus diagnostic module can be optionally installed on the carrier, automatically collecting and distributing diagnostic information for eight field bus segments. By assigning the F8O9F Plus as a field bus device to either one or eight power supply segments, there is no recognition result for the I Tang bus segment, and measurement parameters can be viewed in the Foxborocontrol system. Independent section connections are provided on the substrate. For more information, please refer to the F8O9F Plus product specifications. Redundant 24V DC (nominal.) input power can be connected to the F810 backplane using Foxboro |/a standard amplifier connectors. The F8Ox power module and F809F-Plus fieldbus diagnostic module can be powered by a single power supply, or for devices where the standard Foxboro power supply cannot provide sufficient current capacity, an external 24V DC power supply can be connected. The on-site wiring connection can use pluggable screw terminals (F810-PS) or pluggable spring clip terminals (F810-PC).